@cryptotaxi247 / netdata-1 / commits / 454d5182a

fire alarm if under 100% charge + docs

Chris committed Jul 5, 2018 at 07:48 UTC 454d5182ae6fe804cd2e5ee583f82edc1c08a9d4
1 file changed +3 -1
conf.d/health.d/apcupsd.conf
+3 -1
@@ -13,6 +13,8 @@ template: 10min_ups_load
13 info: average UPS load for the last 10 minutes
14 to: sitemgr
15
16 +# Discussion in https://github.com/firehol/netdata/pull/3928:
17 +# Fire the alarm as soon as it's going on battery (99% charge) and clear only when full.
18 template: ups_charge
19 on: apcupsd.charge
20 os: *
@@ -20,7 +22,7 @@ template: ups_charge
22 lookup: average -60s unaligned of charge
23 units: %
24 every: 60s
23 - warn: $this < (($status >= $WARNING) ? (90) : (98))
25 + warn: $this < 100
26 crit: $this < (($status == $CRITICAL) ? (60) : (50))
27 delay: down 10m multiplier 1.5 max 1h
28 info: current UPS charge, averaged over the last 60 seconds to reduce measurement errors