update tripplite snmp profiles (#20613)
Ilya Mashchenko committed
Jul 1, 2025 at 11:03 UTC
8ac072e08faf8bfe947abb8261b2a68dde5de2e0
2 files changed
+229
-250
src/go/plugin/go.d/config/go.d/snmp.profiles/default/tripplite-pdu.yaml
+103
-128
@@ -10,81 +10,51 @@ metadata:
10
type:
11
value: "PDU"
12
13
+# https://mibbrowser.online/mibdb_search.php?mib=TRIPPLITE-PRODUCTS
14
metrics:
15
- MIB: TRIPPLITE-PRODUCTS
16
table:
17
OID: 1.3.6.1.4.1.850.1.1.1.2
18
name: tlpDeviceTable
19
symbols:
19
- - name: tlpDevice
20
- constant_value_one: true
21
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
20
+ - OID: 1.3.6.1.4.1.850.1.1.1.2.1.10
21
+ name: tlpDeviceStatus
22
+ description: The currently most critical alarm status for the device
23
+ family: Device/Alarm/Status
24
+ unit: "{status}"
25
+ mapping:
26
+ 0: none
27
+ 1: critical
28
+ 2: warning
29
+ 3: info
30
+ 4: status
31
+ 5: offline
32
+ 6: custom
33
+ 7: configuration
34
metric_tags:
23
- - symbol:
35
+ - tag: tlp_device_index
36
+ index: 1
37
+ - tag: _tlp_device_manufacturer
38
+ symbol:
39
OID: 1.3.6.1.4.1.850.1.1.1.2.1.4
40
name: tlpDeviceManufacturer
26
- tag: tlp_device_manufacturer
27
- description: The name of the manufacturer.
28
- unit: "TBD"
29
- - symbol:
41
+ - tag: _tlp_device_model
42
+ symbol:
43
OID: 1.3.6.1.4.1.850.1.1.1.2.1.5
44
name: tlpDeviceModel
32
- tag: tlp_device_model
33
- description: The model designation.
34
- unit: "TBD"
35
- - symbol:
45
+ - tag: _tlp_device_name # A user-supplied name for the device.
46
+ symbol:
47
OID: 1.3.6.1.4.1.850.1.1.1.2.1.6
48
name: tlpDeviceName
38
- tag: tlp_device_name
39
- description: A user-supplied name for the device.
40
- unit: "TBD"
41
- - symbol:
49
+ - tag: _tlp_device_location # A user-supplied location for the device.
50
+ symbol:
51
OID: 1.3.6.1.4.1.850.1.1.1.2.1.8
52
name: tlpDeviceLocation
44
- tag: tlp_device_location
45
- description: A user-supplied location for the device.
46
- unit: "TBD"
47
- - symbol:
53
+ - tag: _tlp_device_region # A user-supplied region for the device.
54
+ symbol:
55
OID: 1.3.6.1.4.1.850.1.1.1.2.1.9
56
name: tlpDeviceRegion
50
- tag: tlp_device_region
51
- description: A user-supplied region for the device.
52
- unit: "TBD"
53
- - symbol:
54
- OID: 1.3.6.1.4.1.850.1.1.1.2.1.10
55
- name: tlpDeviceStatus
56
- tag: tlp_device_status
57
- mapping:
58
- 0: none
59
- 1: critical
60
- 2: warning
61
- 3: info
62
- 4: status
63
- 5: offline
64
- 6: custom
65
- 7: configuration
66
- description: The currently most critical alarm status for the device.
67
- unit: "TBD"
68
- - MIB: TRIPPLITE-PRODUCTS
69
- table:
70
- OID: 1.3.6.1.4.1.850.1.1.2.1
71
- name: tlpDeviceIdentTable
72
- symbols:
73
- - name: tlpDeviceIdent
74
- constant_value_one: true
75
- metric_tags:
76
- - symbol:
77
- OID: 1.3.6.1.4.1.850.1.1.2.1.1.5
78
- name: tlpDeviceIdentSerialNum
79
- tag: tlp_device_ident_serial_num
80
- description: The serial number of the device.
81
- unit: "TBD"
82
- - symbol:
83
- OID: 1.3.6.1.4.1.850.1.1.2.1.1.6
84
- name: tlpDeviceIdentDateInstalled
85
- tag: tlp_device_ident_date_installed
86
- description: The installation date for this device in the format of mm/dd/yyyy.
87
- unit: "TBD"
57
+
58
- MIB: TRIPPLITE-PRODUCTS
59
table:
60
OID: 1.3.6.1.4.1.850.1.1.3.2.2.1
@@ -93,39 +63,44 @@ metrics:
63
- OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.6
64
name: tlpPduDeviceTemperatureC
65
description: The ambient temperature at or near the PDU casing.
66
+ family: Environment/Temperature/Value
67
unit: "Cel"
68
- OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.7
69
name: tlpPduDeviceTemperatureF
70
description: The ambient temperature at or near the PDU casing.
71
+ family: Environment/Temperature/Value
72
unit: "F"
73
- OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.8
74
name: tlpPduDevicePhaseImbalance
75
description: The percentage of imbalance of the three phases.
76
+ family: Phase/Imbalance/Value
77
unit: "%"
78
- OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.9
79
name: tlpPduDeviceOutputPowerTotal
80
description: The AC output total power for all circuits.
81
+ family: Output/Power/Total
82
unit: "W"
109
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
83
+ - OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.1
84
+ name: tlpPduDeviceMainLoadState
85
+ description: The current state of the main output of the device
86
+ family: Output/Main/Status
87
+ unit: "{status}"
88
+ mapping:
89
+ 0: unknown
90
+ 1: off
91
+ 2: on
92
metric_tags:
111
- - index: 1 # tlpDeviceIndex
112
- tag: tlp_device_index
93
+ - tag: tlp_device_index
94
+ index: 1
95
- symbol:
96
OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.11
97
name: tlpPduDeviceOutputCurrentPrecision
116
- tag: tlp_pdu_device_output_current_precision
98
+ tag: _tlp_pdu_device_output_current_precision
99
mapping:
100
0: whole_number
101
1: tenths
102
2: hundredths
121
- - symbol:
122
- OID: 1.3.6.1.4.1.850.1.1.3.2.2.1.1.1
123
- name: tlpPduDeviceMainLoadState
124
- tag: tlp_pdu_device_main_load_state
125
- mapping:
126
- 0: unknown
127
- 1: off
128
- 2: on
103
+
104
- MIB: TRIPPLITE-PRODUCTS
105
table:
106
OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1
@@ -134,40 +109,45 @@ metrics:
109
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.4
110
name: tlpPduOutputVoltage
111
description: The magnitude of the present output voltage for a given output line.
112
+ family: Output/Phase/Voltage/Value
113
unit: "V"
114
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.5
115
name: tlpPduOutputCurrent
116
description: The output current, in hundreths of amps, for a given phase.
117
+ family: Output/Phase/Current/Value
118
unit: "mA"
119
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.10
120
name: tlpPduOutputSource
121
description: The present source of output power.
145
- unit: "TBD"
122
+ family: Output/Source/Status
123
+ unit: "{status}"
124
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.11
125
name: tlpPduOutputFrequency
126
description: The present output frequency.
127
+ family: Output/Frequency/Value
128
unit: "Hz"
129
# TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
130
metric_tags:
152
- - index: 1 # tlpDeviceIndex
153
- tag: tlp_device_index
154
- - index: 2 # tlpPduOutputIndex
155
- tag: tlp_pdu_output_index
156
- - symbol:
131
+ - tag: tlp_device_index
132
+ index: 1 # tlpDeviceIndex
133
+ - tag: tlp_pdu_output_index
134
+ index: 2 # tlpPduOutputIndex
135
+ - tag: tlp_pdu_output_phase
136
+ symbol:
137
OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.2
138
name: tlpPduOutputPhase
159
- tag: tlp_pdu_output_phase
139
mapping:
140
1: phase1
141
2: phase2
142
3: phase3
164
- - symbol:
143
+ - tag: tlp_pdu_output_phase_type
144
+ symbol:
145
OID: 1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.3
146
name: tlpPduOutputPhaseType
167
- tag: tlp_pdu_output_phase_type
147
mapping:
148
0: phase_to_neutral
149
1: phase_to_phase
150
+
151
- MIB: TRIPPLITE-PRODUCTS
152
table:
153
OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1
@@ -176,41 +156,52 @@ metrics:
156
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.4
157
name: tlpPduOutletState
158
description: The current state of the outlet.
179
- unit: "TBD"
159
+ family: Outlet/Operational/Status
160
+ unit: "{status}"
161
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.7
162
name: tlpPduOutletVoltage
163
description: The magnitude of the present output voltage for a given outlet.
164
+ family: Outlet/Voltage/Value
165
unit: "V"
166
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.8
167
name: tlpPduOutletCurrent
168
description: The present output current, in hundreths of amps, of a given outlet.
169
+ family: Outlet/Current/Value
170
unit: "mA"
171
- OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.9
172
name: tlpPduOutletPower
173
description: The output power of a given outlet.
174
+ family: Outlet/Power/Active
175
unit: "W"
176
metric_tags:
193
- - symbol:
177
+ - tag: tlp_pdu_outlet_name
178
+ symbol:
179
OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.2
180
name: tlpPduOutletName
196
- tag: tlp_pdu_outlet_name
197
- - symbol:
181
+ - tag: _tlp_pdu_outlet_description
182
+ symbol:
183
OID: 1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.3
184
name: tlpPduOutletDescription
200
- tag: tlp_pdu_outlet_description
185
+
186
- MIB: TRIPPLITE-PRODUCTS
187
table:
188
OID: 1.3.6.1.4.1.850.1.1.3.2.3.5.1
189
name: tlpPduBreakerTable
190
symbols:
206
- - name: tlpPduBreaker
207
- constant_value_one: true
208
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
191
+ - OID: 1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.2
192
+ name: tlpPduBreakerStatus
193
+ description: The current state of the bank breaker
194
+ family: Breaker/Status
195
+ unit: "{status}"
196
+ mapping:
197
+ 0: open
198
+ 1: closed
199
+ 2: not_installed
200
metric_tags:
210
- - index: 1 # tlpDeviceIndex
211
- tag: tlp_device_index
212
- - index: 2 # tlpPduBreakerIndex
213
- tag: tlp_pdu_breaker_index
201
+ - tag: tlp_device_index
202
+ index: 1 # tlpDeviceIndex
203
+ - tag: tlp_pdu_breaker_index
204
+ index: 2 # tlpPduBreakerIndex
205
- symbol:
206
OID: 1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.2
207
name: tlpPduBreakerStatus
@@ -219,56 +210,40 @@ metrics:
210
0: open
211
1: closed
212
2: not_installed
213
+
214
- MIB: TRIPPLITE-PRODUCTS
215
symbol:
216
OID: 1.3.6.1.4.1.850.1.3.1.0
217
name: tlpAlarmsPresent
218
description: The present number of active alarm conditions.
227
- unit: "{alarm_condition}"
219
+ family: Alarm/Active/Count
220
+ unit: "{alarm}"
221
+
222
- MIB: TRIPPLITE-PRODUCTS
223
table:
224
OID: 1.3.6.1.4.1.850.1.3.2
225
name: tlpAlarmTable
226
symbols:
233
- - name: tlpAlarm
234
- constant_value_one: true
235
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
236
- metric_tags:
237
- - index: 1 # tlpAlarmId
238
- tag: tlp_alarm_id
239
- - symbol:
240
- OID: 1.3.6.1.4.1.850.1.3.2.1.2
241
- name: tlpAlarmDescr
242
- tag: tlp_alarm_descr
243
- description: A reference of the alarm description object.
244
- unit: "TBD"
245
- - symbol:
246
- OID: 1.3.6.1.4.1.850.1.3.2.1.3
247
- name: tlpAlarmTime
248
- tag: tlp_alarm_time
249
- description: The value of sysUpTime when the alarm condition was detected.
250
- unit: "ms"
251
- - symbol:
252
- OID: 1.3.6.1.4.1.850.1.3.2.1.6
253
- name: tlpAlarmDetail
254
- tag: tlp_alarm_detail
255
- description: A textual description of the alarm condition.
256
- unit: "TBD"
257
- - symbol:
258
- OID: 1.3.6.1.4.1.850.1.3.2.1.8
259
- name: tlpAlarmState
260
- tag: tlp_alarm_state
227
+ - OID: 1.3.6.1.4.1.850.1.3.2.1.8
228
+ name: tlpAlarmState
229
+ description: The current state of this alarm condition
230
+ family: Alarm/Condition/Status
231
+ unit: "{status}"
232
mapping:
233
1: active
234
2: inactive
264
- description: The current state of this alarm condition.
265
- unit: "TBD"
266
- - symbol:
267
- OID: 1.3.6.1.4.1.850.1.3.2.1.9
268
- name: tlpAlarmAcknowledged
269
- tag: tlp_alarm_acknowledged
235
+ - OID: 1.3.6.1.4.1.850.1.3.2.1.9
236
+ name: tlpAlarmAcknowledged
237
+ description: Denotes whether the alarm condition has been acknowledged
238
+ family: Alarm/Condition/Acknowledgment/Status
239
+ unit: "{status}"
240
mapping:
241
1: not_acknowledged
242
2: acknowledged
273
- description: Denotes whether the alarm condition has been acknowledged.
274
- unit: "TBD"
243
+ metric_tags:
244
+ - tag: tlp_alarm_index
245
+ index: 1 # tlpAlarmId
246
+ - tag: _tlp_alarm_descr
247
+ symbol:
248
+ OID: 1.3.6.1.4.1.850.1.3.2.1.2
249
+ name: tlpAlarmDescr
src/go/plugin/go.d/config/go.d/snmp.profiles/default/tripplite-ups.yaml
+126
-122
@@ -11,104 +11,120 @@ metadata:
11
type:
12
value: "UPS"
13
14
+metric_tags:
15
+ - tag: tl_ups_ident_serial_num
16
+ OID: 1.3.6.1.4.1.850.100.1.1.2.0
17
+ symbol: tlUpsIdentSerialNum
18
+ - OID: 1.3.6.1.4.1.850.100.1.1.3.0
19
+ symbol: tlUpsIdentID
20
+ tag: tl_ups_ident_id
21
+ - OID: 1.3.6.1.4.1.850.100.1.1.4.0
22
+ symbol: tlUpsSnmpCardSerialNum
23
+ tag: tl_ups_snmp_card_serial_num
24
+ - OID: 1.3.6.1.4.1.850.100.1.1.6.0
25
+ symbol: tlUpsLocation
26
+ tag: tl_ups_location
27
+
28
+# https://mibbrowser.online/mibdb_search.php?mib=TRIPPLITE-12X
29
metrics:
15
-# - MIB: TRIPPLITE-12X
16
-# symbol:
17
-# OID: 1.3.6.1.4.1.850.100.1.12.1.0
18
-# name: tlUpsMainOutletState
19
-# enum:
20
-# unknown: 0
21
-# off: 1
22
-# on: 2
23
-# mixed: 3
24
-# TODO: enum in scalar metric is not supported yet (keep this metric and this
25
-# comment in profile until it's fixed)
30
+ - MIB: TRIPPLITE-12X
31
+ symbol:
32
+ OID: 1.3.6.1.4.1.850.100.1.12.1.0
33
+ name: tlUpsMainOutletState
34
+ description: The current state of the main output of the device
35
+ family: Outlet/Main/Status
36
+ unit: "{status}"
37
+ mapping:
38
+ unknown: 0
39
+ off: 1
40
+ on: 2
41
+ mixed: 3
42
- MIB: TRIPPLITE-12X
43
symbol:
44
OID: 1.3.6.1.4.1.850.100.1.13.1.0
45
name: tlUpsTemperature
30
- description: The ambient temperature
31
- unit: "Cel"
46
+ description: The ambient temperature
47
+ family: Environment/Temperature/Value
48
+ unit: "Cel"
49
- MIB: TRIPPLITE-12X
50
symbol:
51
OID: 1.3.6.1.4.1.850.100.1.2.1.0
52
name: tlUpsBatteryAge # The age of the battery in years.
36
- description: The age of the battery in years
37
- unit: "{year}"
53
+ description: The age of the battery in years
54
+ family: Battery/Age/Internal
55
+ unit: "{year}"
56
- MIB: TRIPPLITE-12X
57
symbol:
58
OID: 1.3.6.1.4.1.850.100.1.2.2.0
59
name: tlUpsTemperatureF
42
- description: The ambient temperature (F)
43
- unit: "degF"
60
+ description: The ambient temperature (F)
61
+ family: Environment/Temperature/Value
62
+ unit: "degF"
63
- MIB: TRIPPLITE-12X
64
symbol:
65
OID: 1.3.6.1.4.1.850.100.1.2.3.0
66
name: tlUpsExternalBatteryAge # The age of the battery in years.
48
- description: The age of external battery in years
49
- unit: "{year}"
67
+ description: The age of external battery in years
68
+ family: Battery/Age/External
69
+ unit: "{year}"
70
- MIB: TRIPPLITE-12X
71
symbol:
72
OID: 1.3.6.1.4.1.850.100.1.6.1.0
73
name: tlUpsAlarmsPresent
54
- description: The present number of active alarm conditions
55
- unit: "{alarm}"
56
-# - MIB: TRIPPLITE-12X
57
-# symbol:
58
-# OID: 1.3.6.1.4.1.850.100.1.7.1.0
59
-# name: tlUpsTestDate # The date of the last self-test run on the ups, in the format YYYYMMDD.
60
-# TODO: this is not a numerical value and possibly not suitable as global metric tags since it might have high cardinality
61
-# - MIB: TRIPPLITE-12X
62
-# symbol:
63
-# OID: 1.3.6.1.4.1.850.100.1.7.2.0
64
-# name: tlUpsTestResultsDetail
65
-# TODO: this is not a numerical value
66
-# - MIB: TRIPPLITE-12X
67
-# symbol:
68
-# OID: 1.3.6.1.4.1.850.100.1.9.1.0
69
-# name: tlUpsConfigBattReplDate # The date on which the battery was last replaced, in the format YYYYMMDD.
70
-# TODO: this is not a numerical value and possibly not suitable as global metric tags since it might have high cardinality
71
-# - MIB: TRIPPLITE-12X
72
-# symbol:
73
-# OID: 1.3.6.1.4.1.850.100.1.9.5.0
74
-# name: tlUpsConfigExternalBattReplDate # The date on which the external battery was last replaced, in the format YYYYMMDD.
75
-# TODO: this is not a numerical value and possibly not suitable as global metric tags since it might have high cardinality
74
+ description: The present number of active alarm conditions
75
+ family: Alarm/Active/Count
76
+ unit: "{alarm}"
77
+ # - MIB: TRIPPLITE-12X
78
+ # symbol:
79
+ # OID: 1.3.6.1.4.1.850.100.1.9.1.0
80
+ # name: tlUpsConfigBattReplDate # The date on which the battery was last replaced, in the format YYYYMMDD.
81
+ # TODO: this is not a numerical value and possibly not suitable as global metric tags since it might have high cardinality
82
+ # - MIB: TRIPPLITE-12X
83
+ # symbol:
84
+ # OID: 1.3.6.1.4.1.850.100.1.9.5.0
85
+ # name: tlUpsConfigExternalBattReplDate # The date on which the external battery was last replaced, in the format YYYYMMDD.
86
+ # TODO: this is not a numerical value and possibly not suitable as global metric tags since it might have high cardinality
87
- MIB: TRIPPLITE-12X
88
symbol:
89
OID: 1.3.6.1.4.1.850.101.1.1.1.0
90
name: tlEnvTemperatureC
80
- description: The ambient temperature (C)
81
- unit: "Cel"
91
+ description: The ambient temperature (C)
92
+ family: Environment/Temperature/Value
93
+ unit: "Cel"
94
- MIB: TRIPPLITE-12X
95
symbol:
96
OID: 1.3.6.1.4.1.850.101.1.1.2.0
97
name: tlEnvTemperatureF
86
- description: The ambient temperature (F)
87
- unit: "degF"
88
-# - MIB: TRIPPLITE-12X
89
-# symbol:
90
-# OID: 1.3.6.1.4.1.850.101.1.1.5.0
91
-# name: tlEnvTemperatureInAlarm
92
-# enum:
93
-# true: 1
94
-# false: 2
95
-# TODO: enum in scalar metric is not supported yet (keep this metric and this
96
-# comment in profile until it's fixed)
98
+ description: The ambient temperature (F)
99
+ family: Environment/Temperature/Value
100
+ unit: "degF"
101
+ - MIB: TRIPPLITE-12X
102
+ symbol:
103
+ OID: 1.3.6.1.4.1.850.101.1.1.5.0
104
+ name: tlEnvTemperatureInAlarm
105
+ description: Indicates whether or not temperature is in alarm
106
+ family: Environment/Temperature/Alarm/Status
107
+ unit: "{status}"
108
+ mapping:
109
+ true: 1
110
+ false: 2
111
- MIB: TRIPPLITE-12X
112
symbol:
113
OID: 1.3.6.1.4.1.850.101.1.2.1.0
114
name: tlEnvHumidity
101
- description: The ambient humidity (%)
102
- unit: "%"
103
-# - MIB: TRIPPLITE-12X
104
-# symbol:
105
-# OID: 1.3.6.1.4.1.850.101.1.2.4.0
106
-# name: tlEnvHumidityInAlarm
107
-# enum:
108
-# true: 1
109
-# false: 2
110
-# TODO: enum in scalar metric is not supported yet (keep this metric and this
111
-# comment in profile until it's fixed)
115
+ description: The ambient humidity (%)
116
+ family: Environment/Humidity/Value
117
+ unit: "%"
118
+ - MIB: TRIPPLITE-12X
119
+ symbol:
120
+ OID: 1.3.6.1.4.1.850.101.1.2.4.0
121
+ name: tlEnvHumidityInAlarm
122
+ description: Indicates whether or not humidity is in alarm
123
+ family: Environment/Humidity/Alarm/Status
124
+ unit: "{status}"
125
+ mapping:
126
+ true: 1
127
+ false: 2
128
- MIB: TRIPPLITE-12X
129
table:
130
OID: 1.3.6.1.4.1.850.100.1.3.2
@@ -117,17 +133,17 @@ metrics:
133
- OID: 1.3.6.1.4.1.850.100.1.3.2.1.3
134
name: tlUpsInputVoltage
135
description: The magnitude of the present input voltage
136
+ family: Input/Voltage/Value
137
unit: "V"
121
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
138
metric_tags:
123
- - symbol:
139
+ - tag: tl_ups_input_voltage_index
140
+ symbol:
141
OID: 1.3.6.1.4.1.850.100.1.3.2.1.1
142
name: tlUpsInputVoltageIndex
126
- tag: tl_ups_input_voltage_index
127
- - symbol:
143
+ - tag: tl_ups_input_voltage_type
144
+ symbol:
145
OID: 1.3.6.1.4.1.850.100.1.3.2.1.2
146
name: tlUpsInputVoltageType
130
- tag: tl_ups_input_voltage_type
147
mapping:
148
0: phase_to_neutral
149
1: phase_to_phase
@@ -138,24 +154,28 @@ metrics:
154
symbols:
155
- OID: 1.3.6.1.4.1.850.100.1.4.7.1.3
156
name: tlUpsOutputCircuitLoadCurrent
141
- description: The magnitude of the present output current in deciamperes
142
- unit: "dA"
157
+ description: The magnitude of the present output current
158
+ family: Output/Circuit/Current/Value
159
+ unit: "A"
160
+ scale_factor: 0.1
161
- OID: 1.3.6.1.4.1.850.100.1.4.7.1.4
162
name: tlUpsOutputCircuitVoltage
145
- description: The magnitude of the present circuit voltage in tenths of an volt
146
- unit: "dV"
163
+ description: The magnitude of the present circuit voltage
164
+ family: Output/Circuit/Voltage/Value
165
+ unit: "V"
166
+ scale_factor: 0.1
167
- OID: 1.3.6.1.4.1.850.100.1.4.7.1.5
168
name: tlUpsOutputCircuitPower
169
description: The magnitude of the present power in watts
170
+ family: Output/Circuit/Power/Active
171
unit: "W"
151
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
172
metric_tags:
153
- - index: 1
154
- tag: tl_ups_output_circuit_index
155
- - symbol:
173
+ - tag: tl_ups_output_circuit_index
174
+ index: 1
175
+ - tag: tl_ups_output_circuit_status
176
+ symbol:
177
OID: 1.3.6.1.4.1.850.100.1.4.7.1.2
178
name: tlUpsOutputCircuitStatus
158
- tag: tl_ups_output_circuit_status
179
mapping:
180
0: open
181
1: closed
@@ -164,64 +184,48 @@ metrics:
184
OID: 1.3.6.1.4.1.850.101.2.1
185
name: tlEnvContactTable
186
symbols:
167
- - name: tlEnvContact
168
- constant_value_one: true
169
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
187
+ - OID: 1.3.6.1.4.1.850.101.2.1.1.3
188
+ name: tlEnvContactStatus
189
+ description: The current status of the contact
190
+ family: Environment/Contact/Status
191
+ unit: "{status}"
192
+ mapping:
193
+ 0: normal
194
+ 1: alarm
195
metric_tags:
171
- - symbol:
196
+ - tag: tl_env_contact_name
197
+ symbol:
198
OID: 1.3.6.1.4.1.850.101.2.1.1.2
199
name: tlEnvContactName
174
- tag: tl_env_contact_name
175
- - symbol:
200
+ - tag: tl_env_contact_config
201
+ symbol:
202
OID: 1.3.6.1.4.1.850.101.2.1.1.4
203
name: tlEnvContactConfig
178
- tag: tl_env_contact_config
204
mapping:
205
0: normally_open
206
1: normally_closed
182
- - symbol:
183
- OID: 1.3.6.1.4.1.850.101.2.1.1.3
184
- name: tlEnvContactStatus
185
- tag: tl_env_contact_status
186
- mapping:
187
- 0: normal
188
- 1: alarm
207
+
208
- MIB: TRIPPLITE-12X
209
table:
210
OID: 1.3.6.1.4.1.850.100.1.10.2
211
name: tlUpsOutletTable
212
symbols:
194
- - name: tlUpsOutlet
195
- constant_value_one: true
196
- metric_tags:
197
- - symbol:
198
- OID: 1.3.6.1.4.1.850.100.1.11.2.1.3
199
- name: tlUpsOutletGroupName
200
- tag: tl_ups_outlet_group_name
201
- - symbol:
202
- OID: 1.3.6.1.4.1.850.100.1.11.2.1.4
203
- name: tlUpsOutletGroupDesc
204
- tag: tl_ups_outlet_group_desc
205
- # TODO: Check out metric_tags with symbols having mappings and/or expressing states/statuses. Need to convert to metrics.
206
- - symbol:
207
- OID: 1.3.6.1.4.1.850.100.1.11.2.1.5
208
- name: tlUpsOutletGroupState
209
- tag: tl_ups_outlet_group_state
213
+ - OID: 1.3.6.1.4.1.850.100.1.11.2.1.5
214
+ name: tlUpsOutletGroupState
215
+ description: The current state of the outlet group
216
+ family: Outlet/Group/Status
217
+ unit: "{status}"
218
mapping:
219
0: unknown
220
1: off
221
2: on
222
3: mixed
215
-metric_tags:
216
- - tag: tl_ups_ident_serial_num
217
- OID: 1.3.6.1.4.1.850.100.1.1.2.0
218
- symbol: tlUpsIdentSerialNum
219
- - OID: 1.3.6.1.4.1.850.100.1.1.3.0
220
- symbol: tlUpsIdentID
221
- tag: tl_ups_ident_id
222
- - OID: 1.3.6.1.4.1.850.100.1.1.4.0
223
- symbol: tlUpsSnmpCardSerialNum
224
- tag: tl_ups_snmp_card_serial_num
225
- - OID: 1.3.6.1.4.1.850.100.1.1.6.0
226
- symbol: tlUpsLocation
227
- tag: tl_ups_location
223
+ metric_tags:
224
+ - tag: tl_ups_outlet_group_name
225
+ symbol:
226
+ OID: 1.3.6.1.4.1.850.100.1.11.2.1.3
227
+ name: tlUpsOutletGroupName
228
+ - tag: tl_ups_outlet_group_desc
229
+ symbol:
230
+ OID: 1.3.6.1.4.1.850.100.1.11.2.1.4
231